(N)YFGY | Three-Core PVC Insulated Cable with Flat Wire Amour
Item descriptions
Application: | To be laid directly in ground, in water, outdoors, indoors and in cable ducts if increased mechanical protection is required or if greater tensile stresses are to be expected during installation and operation. |
Construction: | 1.....stranded bare copper 2.....core insulation of polyvinylchloride (PVC-DIV4) 3.....rubber core covering 4.....inner sheath of polyvinylchloride (PVC-DMV5) 5.....armour of galvanised flat steel wires and counter helix 6.....outer sheath of polyvinylchloride (PVC), red |
Standards: | DIN VDE 0271 DIN VDE 0276-603 DIN EN 60228 class 2 (construction) |
Nominal voltage Uo/U | [V] | 3600 / 6000 Volt | |
Test voltage | [V]AC | 11000 | |
Temperature range | in motion | - 5°C till +70°C | |
fixed | -20°C till +70°C | ||
Operating temperature | short circuit | °C | 160 |
Short circuit time | max. | [sec] | 5 |
Bending radius | in motion | x diameter | 15 |
Flammability | standard | EN 60332-1-2 |
Number of cores and nominal cross section mm² | Copper figure kg/km | Overall diameter appr. mm | Weight appr. kg / km | Current carrying capacity ground A | Current carrying capacity air A |
3 x 50 SM | 1.440,00 | 41 | 3.520 | 175 | 165 |
3 x 70 SM | 2.016,00 | 44 | 4.345 | 220 | 205 |
3 x 95 SM | 2.736,00 | 47 | 5.330 | 260 | 250 |
3 x 120 SM | 3.456,00 | 49 | 6.220 | 295 | 285 |
3 x 150 SM | 4.320,00 | 52 | 7.120 | 335 | 325 |
3 x 185 SM | 5.328,00 | 57 | 8.625 | 370 | 380 |
3 x 240 SM | 6.912,00 | 59 | 9.885 | 425 | 430 |