N2XS(F)2Y | Single-Core XLPE Insulated Cable with PE Outer Sheath, longitudinally watertight (6/10 kV, 12/20 kV, 18/30 kV)
Item descriptions
Application: | To be laid directly in ground, in water, outdoors, indoors and in cable ducts. |
Construction: | 1.....stranded (RM) bare copper wire 2.....inner layer of semi-conducting material 3.....core insullation of cross-linked polyethylene 4.....outer layer of semi-conducting material 5.....swellable tape 6.....screen of copper wires 7.....waterproofing tape 8.....outer sheath of polyethylene (PE), black |
Standards: | DIN VDE 0276-620 HD 620 S1 : 1995 DIN EN 60228 class 2 (construction) |
Test voltage | 6 / 10 kV | [kV] | 21 / 5 min. |
12 / 20 kV | [kV] | 42 / 5 min. | |
18 / 30 kV | [kV] | 63 / 5 min. | |
Temperature range | in motion | -20°C till +90°C | |
fixed | -20°C till +90°C | ||
Operating temperature | short circuit | °C | 250 |
Short circuit time | max. | [sec] | 5 |
Bending radius | min. | x diameter | 15 |
Number of cores and nominal cross section mm² | Copper figure kg/km | Overall diameter appr. mm | Overall diameter max. value appr. mm | Weight appr. kg / km | Current carrying capacity ground A* | Current carrying capacity air A* |
6 / 10 kV | ||||||
1 x 35 RM/16 | 518,40 | 23 | 28 | 820 | 187 | 197 |
1 x 50 RM/16 | 662,40 | 24 | 29 | 960 | 220 | 236 |
1 x 70 RM/16 | 854,40 | 26 | 31 | 1.200 | 268 | 294 |
1 x 95 RM/16 | 1.094,40 | 27 | 32 | 1.450 | 320 | 358 |
1 x 120 RM/16 | 1.334,40 | 29 | 34 | 1.700 | 363 | 413 |
1 x 150 RM/25 | 1.723,20 | 30 | 35 | 2.000 | 405 | 468 |
1 x 185 RM/25 | 2.059,20 | 32 | 37 | 2.350 | 456 | 535 |
1 x 240 RM/25 | 2.587,20 | 34 | 39 | 2.900 | 526 | 631 |
1 x 300 RM/25 | 3.163,20 | 36 | 41 | 3.550 | 591 | 722 |
1 x 400 RM/35 | 4.233,60 | 40 | 45 | 4.500 | 662 | 827 |
1 x 500 RM/35 | 5.193,60 | 43 | 48 | 5.550 | 744 | 949 |
Number of cores and nominal cross section mm² | Copper figure kg/km | Overall diameter appr. mm | Overall diameter max. value appr. mm | Weight appr. kg / km | Current carrying capacity ground A* | Current carrying capacity air A* |
12 / 20 kV | ||||||
1 x 50 RM/16 | 662,40 | 28 | 33 | 1.150 | 222 | 239 |
1 x 70 RM/16 | 854,40 | 30 | 35 | 1.350 | 271 | 297 |
1 x 95 RM/16 | 1.094,40 | 31 | 36 | 1.600 | 232 | 361 |
1 x 120 RM/16 | 1.334,40 | 33 | 38 | 1.850 | 367 | 416 |
1 x 150 RM/25 | 1.723,20 | 34 | 39 | 2.250 | 409 | 470 |
1 x 185 RM/25 | 2.059,20 | 36 | 41 | 2.600 | 461 | 538 |
1 x 240 RM/25 | 2.587,20 | 39 | 44 | 3.150 | 532 | 634 |
1 x 300 RM/25 | 3.163,20 | 41 | 46 | 3.800 | 599 | 724 |
1 x 400 RM/35 | 4.233,60 | 44 | 49 | 4.750 | 671 | 829 |
1 x 500 RM/25 | 5.193,60 | 47 | 52 | 6.450 | 750 | 927 |
Number of cores and nominal cross section mm² | Copper figure kg/km | Overall diameter appr. mm | Overall diameter max. value appr. mm | Weight appr. kg / km | Current carrying capacity ground A* | Current carrying capacity air A* |
18 / 30 kV | ||||||
1 x 50 RM/16 | 662,40 | 33 | 38 | 1.350 | 225 | 241 |
1 x 95 RM/16 | 1.094,40 | 36 | 41 | 1.900 | 327 | 363 |
1 x 120 RM/16 | 1.334,40 | 38 | 43 | 2.200 | 371 | 418 |
1 x 150 RM/25 | 1.723,20 | 39 | 44 | 2.550 | 414 | 472 |
1 x 185 RM/25 | 2.059,20 | 41 | 46 | 2.950 | 466 | 539 |
1 x 240 RM/25 | 2.587,20 | 43 | 48 | 3.500 | 539 | 635 |
1 x 300 RM/25 | 3.163,20 | 46 | 51 | 4.150 | 606 | 725 |
1 x 400 RM/25 | 4.233,60 | 49 | 54 | 5.050 | 680 | 831 |
1 x 500 RM/35 | 5.193,60 | 52 | 57 | 6.200 | 765 | 953 |