H05V-K | PVC Insulated Single Core Wire
Item descriptions
Application: | For protected fixed installations inside appliances and in or on lighting fittings. For installations in pipes on and under plaster, however, only for signal circuit. |
Construction: | 1.....fine stranded bare cooper 2.....PVC insulation |
Standards: | DIN VDE 0281-3 DIN EN 60228 Class 5 (construction) |
Nominal voltage Uo/U | [V] | 300 / 500 Volt | |
Test voltage | [V]AC | 2000 | |
Temperature range | in motion | +5°C till +70°C | |
Operating temperature | short circuit | °C | 160 |
Short circuit time | max. | [sec] | 5 |
Bending radius | min. | x diameter | 4 |
Flammability | standard | EN 60332-1-2 |
Nominal cross section mm² | Colours | Copper figure kg/km | Cond. construction (appr. value) mm | Overall diameter appr. mm | Weight appr. kg / km |
one coloured und yellow-green | |||||
0,50 | bk/b/br | 4,80 | 16 x 0,21 | 2,2 | 10,0 |
yg/dbl/gr/lgy/vi/wt | 4,80 | 16 x 0,21 | 2,2 | 10,0 | |
or/gn/ye/rd/pk/tra | 4,80 | 16 x 0,21 | 2,2 | 10,0 | |
0,75 | bk/bl/br | 7,20 | 24 x 0,21 | 2,4 | 12,0 |
yg/dbl/lbl/gr | 7,20 | 24 x 0,21 | 2,4 | 12,0 | |
vi/wt/or/gn/rd | 7,20 | 24 x 0,21 | 2,4 | 12,0 | |
1 | bk/bl/br | 9,60 | 32 x 0,21 | 2,6 | 14,0 |
yg/dbl/lbl/gr/vi | 9,60 | 32 x 0,21 | 2,6 | 14,0 | |
wt/or/gn/ye/rd | 9,60 | 32 x 0,21 | 2,6 | 14,0 | |
two coloured construction | |||||
0,50 | blwt/rdwt/rdye | 4,80 | 16 x 0,21 | 2,2 | 10,0 |
bkye/bkwt | 4,80 | 16 x 0,21 | 2,2 | 10,0 | |
0,75 | blrd/blwt/wtbr | 7,20 | 24 x 0,21 | 2,4 | 12,0 |
dblwt/rdwt/gnwt | 7,20 | 24 x 0,21 | 2,4 | 12,0 | |
gnbk/rdbk | 7,20 | 24 x 0,21 | 2,4 | 12,0 | |
1 | blwt/rdwt/brwt | 9,60 | 32 x 0,21 | 2,6 | 14,0 |
bkwt/yebk/vibk | 9,60 | 32 x 0,21 | 2,6 | 14,0 | |
blbk/brbk/viwt | 9,60 | 32 x 0,21 | 2,6 | 14,0 |