(N)YM(ST)-J | PVC Sheathed Wire with Screen Bio Wire
Item descriptions
Application: | Suitable where effective limitation of electro-magnetic interference fields is necessary, for installations in dry, humid and wet locations. Not suitable for laying directly open-air or in concrete. Not suitable in areas with explosion hazard. |
Construction: | 1.....solid bare copper 2.....polyvinylchloride (PVC) insulation 3.....screen of plastic coated aluminium tape with tinned drain wire 4.....polyvinylchloride (PVC) outer sheath, grey |
Standards: | adapted to DIN VDE 250-204 DIN EN 60228 Class 1 (construction) HD 308 S2 (core identification) |
Nominal voltage Uo/U | [V] | 300 / 500 Volt | |
Test voltage | [V]AC | 2000 | |
Temperature range | in motion | +5°C till +70°C | |
Operating temperature | short circuit | °C | 160 |
Short circuit time | max. | [sec] | 5 |
Flammability | standard | EN 60332-1-2 |
Number of cores and nominal cross section mm² | Copper figure kg/km | Cond. construcion (appr. value) mm | Overall diameter appr. mm | Calorific potential kWh / m | Weight appr. kg / km |
3 x 1,5 / 1,5 | 52,80 | 1 x 1,38 | 10,5 | 0,44 | 140 |
4 x 1,5 / 1,5 | 65,28 | 1 x 1,38 | 11,5 | 0,53 | 188 |
5 x 1,5 / 1,5 | 79,68 | 1 x 1,38 | 12,0 | 0,58 | 216 |
7 x 1,5 / 1,5 | 108,48 | 1 x 1,38 | 13,0 | 0,67 | 263 |
3 x 2,5 / 1,5 | 79,68 | 1 x 1,78 | 12,0 | 0,58 | 214 |
5 x 2,5 / 1,5 | 127,68 | 1 x 1,78 | 13,5 | 0,75 | 300 |