YMT | PVC - Cable with Steel Carrier
Item descriptions
Application: | Usable as a self-supporting circuit on free power mains, in accordance with applicable regulation. They may not be installed directly into the ground. |
Construction: | 1.....bare copper, solid (RE) or stranded (RM) 2.....polyvinylchloride (PVC) insulation 3.....carrier cable steel-reinforced, stranded 4.....bedding 5.....polyvinylchloride (PVC) outer sheath, black |
Information: | The minimum value for the breaking force of the supporting element amounts to: 6.000 N at the 3x2,5 and 5x2,5 mm² 10.500 N at the 4x10 and 4x16 mm² Information according to DIN VDE 0250-206 |
Standards: | according to ÖVE K41 DIN 57250 part 206 DIN VDE 250-206 DIN EN 60228 class 1 and 2 (construction) HD 308 S2 (core identification) |
Nominal voltage Uo/U | [V] | 300 / 500 Volt | |
Test voltage | [V]AC | 4000 | |
Temperature range | in motion | +5°C till +70°C | |
fixed | -40°C till +70°C | ||
Operating temperature | short circuit | °C | 160 |
Short circuit time | max. | [sec] | 5 |
Bending radius | in motion | x diameter | 4 |
Flammability | standard | EN 60332-1-2 |
Number of cores and nominal cross section mm² | Copper figure kg/km | Overall measures appr. mm | Weight appr. kg/km | |||
3 x 2,5 RE | 72,00 | 12,5 x 20,5 | 190 | |||
4 x 10 RM | 384,00 | 19,0 x 28,0 | 960 | |||
4 x 16 RM | 614,40 | 22,0 x 32,0 | 1.320 | |||
5 x 2,5 RE | 120,00 | 14,5 x 23,0 | 361 | |||
5 x 10 RM | 480,00 | 21,0 x 32,0 | 993 | |||