N07V3V3-F | PVC Building Site Cable
Item descriptions
Application: | This cable is suitable for connecting electrical equipment particularly on building sites. It is used in dry and damp locations, outdoors and in areas with explosion hazard. |
Construction: | 1.....fine-stranded bare copper 2.....core insulation of cold-resistant polyvinylchloride(PVC) 3.....outer sheath of cold-resistant polyvinylchloride (PVC), yellow |
Standards: | HD 21.13.S1 1995 ÖNORM E8241-55 DIN EN 60228 class 5 (construction) HD 308 S2 (core identification) |
Nominal voltage Uo/U | [V] | 450 / 750 Volt | |
Test voltage | [V]AC | 2500 | |
Temperature range | in motion | -35°C till +70°C | |
Operating temperature | short circuit | °C | 160 |
Short circuit time | max. | [sec] | 5 |
Bending radius | min. | x diameter | 6 |
Flammability | standard | EN 60332-1-2 |
Number of cores and nominal cross section mm² | Copper figure kg/km | Cond. construction (appr. value) mm | Overall diameter appr. mm | Weight appr. kg / km |
2 X 1,5 | 28,80 | 30 x 0,26 | 9,0 | 85 |
3 G 1,5 | 43,20 | 30 x 0,26 | 10,5 | 132 |
4 G 1,5 | 57,60 | 30 x 0,26 | 11,6 | 161 |
5 G 1,5 | 72,00 | 30 x 0,26 | 12,8 | 185 |
3 G 2,5 | 72,00 | 50 x 0,26 | 12,4 | 197 |
4 G 2,5 | 96,00 | 50 x 0,26 | 13,8 | 238 |
5 G 2,5 | 120,00 | 50 x 0,26 | 15,2 | 291 |
5 G 4 | 192,00 | 56 x 0,31 | 17,8 | 420 |
5 G 6 | 288,00 | 84 x 0,31 | 19,9 | 598 |
5 G 10 | 480,00 | 80 x 0,41 | 26,0 | 1.051 |
5 G 16 | 768,00 | 128 x 0,41 | 29,9 | 1.442 |