SLM 0,6/1 kV | PVC Composite Connection Cable
Item descriptions
Application: | These connection cables are well suited for fixed installations and for flexible use e.g. in machine and plant engineering for medium level mechanical stress in dry, damp and wet locations. |
Construction: | 1.....fine-stranded bare copper 2.....core insulation of polyvinylchloride (PVC) 3.....outer sheath of polyvinylchloride (PVC) grey or black, increased oil resistant |
Standards: | DIN EN 60228 class 5 (construction) HD 308 S2 (core identification) core identification: 1 core green/yellow, other cores black with figures |
Nominal voltage Uo/U | [V] | 600 / 1000 Volt | |
Test voltage | [V]AC | 4000 | |
Temperature range | in motion | -5°C till +70°C | |
fixed | -30°C till +70°C | ||
Bending radius | one time / fixed | x diameter | 5,0 |
in motion | x diameter | 7,5 | |
Flammability | standard | EN 60332-1-2 |
Number of cores and nominal cross section mm² | Copper figure kg/km | Cond. construction (appr. value) mm | Overall diameter mm | Weight appr. kg / km |
4 x 1,5 | 57,60 | 30 x 0,26 | 10,7 | 176 |
4 x 2,5 | 96,00 | 48 x 0,26 | 10,7 | 242 |
4 x 4 | 153,60 | 56 x 0,31 | 13,7 | 330 |
4 x 6 | 230,40 | 84 x 0,31 | 15,0 | 428 |
4 x 10 | 384,00 | 80 x 0,41 | 18,3 | 668 |
4 x 16 | 614,40 | 128 x 0,41 | 20,7 | 941 |
4 x 25 | 960,00 | 200 x 0,41 | 25,2 | 1.431 |
5 x 4 | 192,00 | 56 x 0,31 | 14,9 | 400 |
5 x 6 | 288,00 | 84 x 0,31 | 16,4 | 523 |
5 x 10 | 480,00 | 80 x 0,41 | 20,2 | 820 |