SiA | Silicone Insulated Wire
Item descriptions
Application: | This wire is well suited for internal wiring in lamps, instruments, control panels and distributors for low mechanical stress particularly at high ambient temperatures. |
Construction: | 1.....solid tinned copper 2.....core insulation of silicone (2GI1) |
Standards: | DIN EN 60228 Class 1 (construction) |
Nominal voltage Uo/U | [V] | 300 / 500 Volt | |
Test voltage | [V]AC | 2000 | |
Temperature range | in motion | -60°C till +180°C | |
temporary resilient | +250°C | ||
Flammability | standard | EN 60332-1-2 |
Nominal cross section mm² | Colours | Copper figure kg/km | Cond. construction (appr. value) mm | Overall diameter mm | Weight appr. kg / km |
0,75 | bk/bl/br/yg/gr/wt/rd | 7,20 | 1 x 0,98 | 2,2 | 12 |
1 | bk/bl/br/yg/wt | 9,60 | 1 x 1,13 | 2,3 | 15 |
1,5 | bk/bl/br/yg/wt/rd | 14,40 | 1 x 1,38 | 2,6 | 20 |
2,5 | bk/bl/yg | 24,00 | 1 x 1,78 | 3,2 | 33 |
4 | bk | 38,40 | 1 x 2,26 | 3,9 | 51 |
6 | bk | 57,60 | 1 x 2,76 | 4,4 | 72 |
10 | bk | 96,00 | 1 x 3,57 | 5,6 | 120 |