SiF/ GL | Silicone Insulated Wire with Fibreglass Braiding
Item descriptions
Application: | This wire is well suited for internal wiring in lamps, instruments, control panels and distributors. It is used for high mechanical stress, as the fibreglass braiding protects the silicone insulation from mechanical damages. It is halogen-free and heat resistant. |
Construction: | 1.....fine-stranded tinned or bare copper 2.....core insulation silicon (2GI1) 3.....impregnated fibreglass braiding |
Standards: | DIN EN 60228 Class 5 (construction) |
Nominal voltage Uo/U | [V] | 300 / 500 Volt | |
Test voltage | [V]AC | 2000 | |
Temperature range | in motion | -60°C till +180°C | |
temporary resilient | +250°C | ||
Flammability | standard | EN 60332-1-2 |
Nominal cross section mm² | Colours | Copper figure kg/km | Cond. construction (appr. value) mm | Overall diameter mm | Weight appr. kg / km |
0,75 | ws | 7,20 | 24 x 0,21 | 2,7 | 15 |
1 | ws | 9,60 | 32 x 0,21 | 2,8 | 18 |
1,5 | ws | 14,40 | 30 x 0,26 | 3,3 | 26 |
2,5 | ws | 24,00 | 50 x 0,26 | 3,9 | 38 |
4 | ws | 38,40 | 56 x 0,31 | 4,5 | 55 |
6 | ws | 57,60 | 84 x 0,31 | 5,2 | 76 |
10 | ws | 96,00 | 80 x 0,41 | 7,3 | 136 |
16 | ws | 153,60 | 128 x 0,41 | 8,3 | 200 |
25 | ws | 240,00 | 200 x 0,41 | 10,2 | 311 |
35 | ws | 336,00 | 280 x 0,41 | 11,4 | 412 |
50 | ws | 480,00 | 400 x 0,41 | 14,1 | 583 |
70 | ws | 672,00 | 356 x 0,51 | 16,1 | 798 |
95 | ws | 912,00 | 495 x 0,51 | 18,5 | 1.073 |
120 | ws | 1.152,00 | 614 x 0,51 | 20,0 | 1.329 |