E-Y2Y | PVC Insulated Heavy Current Cable with Copper Conductor and PE Outer Sheath
Item descriptions
Application: | This power cable is suitable for fixed installations, preferably in cable ducts, indoors, outdoors, in water or underground if no mechanical damage is to be expected. |
Construction: | 1.....solid (RE) or stranded (RM/SM) bare copper 2.....core insulation of polyvinylchloride (PVC) 3.....PVC core covering or taping 4.....outer sheath of polyethylene (PE), black, Shore-hardness > 55 UV-resistant |
Standards: | ÖVE K 23 and K 603 HD 603 S1:1994 + A2:2003 DIN EN 60228 class 1 and 2 (construction) HD 308 S2 (core identification) |
Nominal voltage Uo/U | [V] | 600 / 1000 Volt | |
Test voltage | [V]AC | 4000 | |
Temperature range | in motion | - 5°C till +70°C | |
fixed | -20°C till +70°C | ||
Operating temperature | short circuit | °C | 160 |
Short circuit time | max. | [sec] | 5 |
Bending radius | single-core style | x diameter | 15 |
multi-core style | x diameter | 12 | |
Flammability | standard | EN 60332-1-2 |
Number of cores and nominal cross section mm² | Copper figure kg/km | Overall diameter appr. mm | Weight appr. kg / km | Current carrying capacity ground A | Current carrying capacity air A |
4 x 6 RE | 230,40 | 15 | 570 | 56 | 43 |
4 x 10 RE | 384,00 | 20 | 775 | 75 | 60 |
4 x 10 RM | 384,00 | 20 | 775 | 75 | 60 |
4 x 16 RE | 614,40 | 21 | 1.100 | 98 | 80 |
4 x 16 RM | 614,40 | 22 | 1.100 | 98 | 80 |
4 x 25 RM | 960,00 | 25 | 1.632 | 128 | 106 |
4 x 35 SM | 1.344,00 | 27 | 1.959 | 157 | 131 |
4 x 50 SM | 1.920,00 | 32 | 2.595 | 185 | 159 |
5 x 6 RE | 288,00 | 17 | 672 | * | * |
5 x 10 RE | 480,00 | 21 | 921 | * | * |