E-AY2Y | PVC Insulated Heavy Current Cable with Aluminium Conductor and PE Outer Sheath
Item descriptions
Application: | This power cable is suitable for fixed installations in cable ducts outdoors, in water or underground if no mechanical damage is to be expected. |
Construction: | 1.....solid (RE/SE) or stranded (RM/SM) aluminium wire 2.....core insulation of polyvinylchloride (PVC) 3.....PVC core covering or taping 4.....outer sheath of polyethylene (PE), black, Shore-hardness HD 55-60 UV-resistant |
Standards: | ÖVE K 23 and K 603 HD 603 S1 DIN EN 60228 class 1 and 2 (construction) HD 308 S2 (core identification) |
Nominal voltage Uo/U | [V] | 600 / 1000 Volt | |
Test voltage | [V]AC | 4000 | |
Temperature range | in motion | - 5°C till +70°C | |
fixed | -20°C till +70°C | ||
Operating temperature | short circuit | °C | 160 |
Bending radius | single-core style | x diameter | 15 |
multi-core style | x diameter | 12 | |
Short circuit time | max. | [sec] | 5 |
Flammability | standard | EN 60332-1-2 |
Number of cores and nominal cross section mm² | Aluminium figure kg/km | Overall diameter appr. mm | Weight appr. kg / km | Current carrying capacity ground A | Current carrying capacity air A |
1 x 120 RM | 348 | 20 | 525 | 389 | 302 |
3 x 240/120 SM | 2.470 | 55 | 3.994 | 364 | 338 |
4 x 25 RE | 294 | 24 | 769 | 102 | 82 |
4 x 50 SE | 588 | 28 | 1.093 | 144 | 119 |
4 x 95 SE | 1.117 | 37 | 1.930 | 215 | 186 |
4 x 150 SE | 1.764 | 45 | 2.822 | 275 | 246 |
4 x 25 RM | 294 | 24 | 769 | 102 | 82 |
4 x 35 SM | 412 | 25 | 868 | 123 | 100 |
4 x 50 SM | 588 | 28 | 1.091 | 144 | 119 |
4 x 95 SM | 1.117 | 37 | 1.930 | 215 | 186 |
4 x 150 SM | 1.764 | 43 | 2.449 | 275 | 246 |
4 x 185 SM | 2.176 | 48 | 3.075 | 313 | 285 |
4 x 240 SM | 2.822 | 57 | 4.509 | 364 | 338 |