E-A2Y | PE Insulated Overhead Line
Item descriptions
Application: | This overhead line is particularly suited as a roof pylon cable outdoors, but not underground. |
Construction: | 1.....stranded compacted aluminium wires 2.....outer sheath of polyethylene (PE), black |
Info: | NFA2X on request |
Standards: | ÖVE / ÖNORM E8200-626 HD 626 S1 |
Nominal voltage Uo/U | [V] | 600 / 1000 Volt | |
Test voltage | [V]AC | 3500 | |
Temperature range | in motion | -20°C till +90°C | |
Operating temperature | short circuit | °C | 120 |
Short circuit time | max. | [sec] | 5 |
Bending radius | in motion | x diameter | 18 |
Number of cores and nominal cross section mm² | Aluminium figure kg/km | max. overall diameter of insulation appr. mm | Overall diameter appr. mm | Weight appr. kg / km | Current carrying capacity air A |
2 x 25 RM | 147 | 9 | 17,4 | 210 | 80 |
4 x 25 RM | 294 | 9 | 21,0 | 420 | 80 |
4 x 50 RM | 588 | 13 | 27,5 | 740 | 125 |
4 x 70 RM | 823 | 14 | 31,9 | 1.000 | 160 |
4 x 95 RM | 1.117 | 16 | 36,7 | 1.350 | 185 |