E-YCY | PVC Insulated Cable with Concentric Conductor Screen Cross Section 16 mm²
Item descriptions
Application: | In dry, humid and wet locations, cable ducts, outdoors, underground and in water. |
Construction: | 1.....solid (RE) or stranded (RM/SM) bare copper 2.....core insulation of polyvinylchloride (PVC) 3.....PVC core covering or taping 4.....concentric conductor of copper wires and copper tape 5.....outer sheath of polyvinylchloride (PVC), black |
Standards: | DIN VDE 0276-603 DIN EN 60228 class 1 (construction) HD 308 S2 (core identification) |
Nominal voltage Uo/U | [V] | 600 / 1000 Volt | |
Test voltage | [V]AC | 4000 | |
Temperature range | in motion | - 5°C till +70°C | |
fixed | -20°C till +70°C | ||
Operating temperature | short circuit | °C | 160 |
Short circuit time | max. | [sec] | 5 |
Bending radius | one time / fixed | x diameter | 12 |
Bending radius | in motion | x diameter | 15 |
Flammability | standard | EN 60332-1-2 |
Number of cores and nominal cross section mm² | Copper figure kg/km | Overall diameter appr. mm | Weight appr. kg / km | Current carrying capacity ground A | Current carrying capacity air A | ||||||||||||||
4 x 1,5 RE/ 16 | 240,00 | 15 | 260 | 26 | 18 | ||||||||||||||
7 x 1,5 RE/ 16 | 283,20 | 17 | 540 | * | * | ||||||||||||||
10 x 1,5 RE/ 16 | 326,40 | 20 | 660 | * | * | ||||||||||||||
12 x 1,5 RE/ 16 | 355,20 | 20 | 700 | * | * | ||||||||||||||
14 x 1,5 RE/ 16 | 384,00 | 21 | 750 | * | * | ||||||||||||||
19 x 1,5 RE/ 16 | 456,00 | 23 | 900 | * | * | ||||||||||||||
24 x 1,5 RE/ 16 | 528,00 | 27 | 1.110 | * | * | ||||||||||||||
30 x 1,5 RE/ 16 | 614,40 | 28 | 1.260 | * | * | ||||||||||||||
3 x 2,5 RE/ 16 | 228,48 | 14 | 459 | 27 | 19 | ||||||||||||||
4 x 2,5 RE/ 16 | 278,40 | 16 | 330 | 34 | 25 | ||||||||||||||
5 x 2,5 RE/ 16 | 302,40 | 17 | 580 | * | * | ||||||||||||||
7 x 2,5 RE/ 16 | 350,40 | 18 | 630 | * | * | ||||||||||||||
10 x 2,5 RE/ 16 | 422,40 | 21 | 800 | * | * | ||||||||||||||
12 x 2,5 RE/ 16 | 470,40 | 22 | 890 | * | * | ||||||||||||||
14 x 2,5 RE/ 16 | 518,40 | 23 | 980 | * | * | ||||||||||||||
19 x 2,5 RE/ 16 | 638,40 | 26 | 1.180 | * | * | ||||||||||||||
24 x 2,5 RE/ 16 | 758,40 | 29 | 1.450 | * | * | ||||||||||||||
Number of cores and nominal cross section mm² | Copper figure kg/km | Overall diameter appr. mm | Weight appr. kg / km | Current carrying capacity ground A | Current carrying capacity air A | ||||||||||||||
30 x 2,5 RE/ 16 | 902,40 | 30 | 1.630 | * | * | ||||||||||||||
2 x 4 RE/ 16 | 259,20 | 16 | 510 | 44 | 34 | ||||||||||||||
4 x 4 RE/ 16 | 336,00 | 18 | 630 | 44 | 34 | ||||||||||||||
5 x 4 RE/ 16 | 374,40 | 19 | 730 | * | * | ||||||||||||||
7 x 4 RE/ 16 | 451,20 | 24 | 950 | * | * | ||||||||||||||
2 x 6 RE/ 16 | 299,52 | 17 | 580 | 56 | 43 | ||||||||||||||
4 x 6 RE/ 16 | 412,80 | 19 | 750 | 56 | 43 | ||||||||||||||
5 x 6 RE/ 16 | 470,40 | 21 | 860 | * | * | ||||||||||||||
4 x 10 RE/ 16 | 566,40 | 22 | 970 | 75 | 60 | ||||||||||||||
5 x 10 RM/ 16 | 662,40 | 25 | 1.200 | * | * | ||||||||||||||
5 x 16 RM/ 16 | 950,40 | 27 | 1.475 | * | * | ||||||||||||||