NA2XSY | XLPE Insulated Single-Core Cable with PVC Outer Sheath
Item descriptions
Application: | To be laid directly in ground, outdoors, indoors and in cable ducts. |
Construction: | 1.....stranded (RM) aluminium wires 2.....inner layer of semi-conducting material 3.....core insulation of cross-linked polyethylene 4.....outer layer of semi-conducting material 5.....screen of copper wires 6.....outer sheath of polyvinylchloride (PVC), red |
Standards: | DIN VDE0276-620 HD 620 S1: 1995 DIN EN 60228 class 2 (construction) |
Test voltage | 6 / 10 kV | [kV] | 21 / 5 min. |
12 / 20 kV | [kV] | 42 / 5 min. | |
18 / 30 kV | [kV] | 63 / 5 min. | |
Temperature range | in motion | - 5°C till +70°C | |
fixed | -20°C till +70°C | ||
Operating temperature | short circuit | °C | 250 |
Short circuit time | max. | [sec] | 5 |
Bending radius | min. | x diameter | 15 |
Flammability | standard | EN 60332-1-2 |
Number of cores and nominal cross section mm² | Aluminium figure kg/km | Copper figure kg/km | Overall diameter appr. mm | Overall diameter max. value appr. mm | Weight appr. kg / km | Current carrying capacity ground A* | Current carrying capacity air A* |
6 / 10 kV | |||||||
1 x 35 RM/16 | 103 | 182,40 | 23 | 28 | 700 | 145 | 153 |
1 x 50 RM/16 | 147 | 182,40 | 24 | 29 | 750 | 171 | 183 |
1 x 70 RM/16 | 206 | 182,40 | 26 | 31 | 850 | 208 | 228 |
1 x 95 RM/16 | 279 | 182,40 | 27 | 32 | 950 | 248 | 278 |
1 x 120 RM/16 | 353 | 182,40 | 29 | 34 | 1.050 | 283 | 321 |
1 x 150 RM/25 | 441 | 283,20 | 30 | 35 | 1.300 | 315 | 364 |
1 x 185 RM/25 | 544 | 283,20 | 32 | 37 | 1.400 | 357 | 418 |
1 x 240 RM/25 | 706 | 283,20 | 34 | 39 | 1.650 | 413 | 494 |
1 x 300 RM/25 | 882 | 283,20 | 36 | 40 | 1.850 | 466 | 568 |
1 x 400 RM/35 | 1.176 | 393,60 | 40 | 45 | 2.300 | 529 | 660 |
Number of cores and nominal cross section mm² | Aluminium figure kg/km | Copper figure kg/km | Overall diameter appr. mm | Overall diameter max. value appr. mm | Weight appr. kg / km | Current carrying capacity ground A* | Current carrying capacity air A* |
12 / 20 kV | |||||||
1 x 50 RM/16 | 147 | 182,40 | 28 | 33 | 950 | 172 | 185 |
1 x 70 RM/16 | 206 | 182,40 | 30 | 35 | 1.050 | 210 | 231 |
1 x 95 RM/16 | 279 | 182,40 | 31 | 36 | 1.150 | 251 | 280 |
1 x 120 RM/16 | 353 | 182,40 | 33 | 38 | 1.300 | 285 | 323 |
1 x 150 RM/25 | 441 | 283,20 | 34 | 39 | 1.500 | 319 | 366 |
1 x 185 RM/25 | 544 | 283,20 | 36 | 41 | 1.650 | 361 | 420 |
1 x 240 RM/25 | 706 | 283,20 | 39 | 44 | 1.850 | 417 | 496 |
1 x 300 RM/25 | 882 | 283,20 | 41 | 46 | 2.100 | 471 | 569 |
1 x 400 RM/35 | 1.176 | 393,60 | 44 | 49 | 2.550 | 535 | 660 |
Number of cores and nominal cross section mm² | Aluminium figure kg/km | Copper figure kg/km | Overall diameter appr. mm | Overall diameter max. value appr. mm | Weight appr. kg / km | Current carrying capacity ground A* | Current carrying capacity air A* |
18 / 30 kV | |||||||
1 x 50 RM/16 | 147 | 182,40 | 36 | 41 | 1.190 | 175 | 187 |
1 x 70 RM/16 | 206 | 182,40 | 37 | 42 | 1.315 | 214 | 232 |
1 x 95 RM/16 | 279 | 182,40 | 39 | 43 | 1.450 | 256 | 281 |
1 x 120 RM/16 | 353 | 182,40 | 40 | 45 | 1.580 | 290 | 323 |
1 x 150 RM/25 | 441 | 283,20 | 42 | 47 | 1.800 | 324 | 365 |
1 x 185 RM/25 | 544 | 283,20 | 44 | 49 | 1.965 | 366 | 418 |
1 x 240 RM/25 | 706 | 283,20 | 46 | 51 | 2.230 | 426 | 494 |
1 x 300 RM/25 | 882 | 283,20 | 49 | 53 | 2.470 | 479 | 564 |
1 x 400 RM/35 | 1.176 | 393,60 | 51 | 56 | 2.920 | 545 | 654 |