H07Z-K | Halogen-Free Single Core Wire
Item descriptions
Application: | For the installation in electrical conduit on or under plaster or in similar closed systems especially for applications where there is a requirement for low smoke and corrosive gas creation in the event of fire, however not outside. |
Construction: | 1.....fine-stranded tinned or bare copper 2.....core insulation of halogen-free, cross-linked polyolefin copolymerisate (EI5) |
Standards: | DIN VDE 0282-9 HD 22.9 S2+A1 DIN EN 60228 class 5 (construction) |
Nominal voltage Uo/U | [V] | 450 / 750 Volt | |
Test voltage | [V]AC | 2500 | |
Temperature range | fixed | +5°C till +90°C | |
Operating temperature | short circuit | °C | 250 |
Short circuit time | max. | [sec] | 5 |
Bending radius | one time / fixed | x diameter | 6 |
Flammability | standard | EN 60332-1 IEC 60332-1 |
Nominal cross section mm² | Colours | Copper figure kg/km | Overall diameter appr.mm | Calorific potential kWh / m | Weight appr. kg / km |
1,5 | bk/bl/br/dbl | 14,40 | 2,9 | 0,40 | 20 |
yg/gr/wt/or/rd | 14,40 | 2,9 | 0,40 | 20 | |
2,5 | bk/bl/lbl/br | 24,00 | 3,6 | 0,49 | 32 |
yg/gy/rd | 24,00 | 3,6 | 0,49 | 32 | |
4 | bk/bl/br | 38,40 | 4,1 | 0,59 | 46 |
yg/gy/rd | 38,40 | 4,1 | 0,59 | 46 | |
6 | bk/bl/br | 57,60 | 4,8 | 0,71 | 65 |
yg/gy/rd | 57,60 | 4,8 | 0,71 | 65 | |
10 | bk/bl | 96,00 | 6,3 | 0,89 | 111 |
yg | 96,00 | 6,3 | 0,89 | 111 | |
16 | bk/bl/br | 153,60 | 7,2 | 1,20 | 166 |
yg | 153,60 | 7,2 | 1,20 | 166 | |
25 | bk/bl/br | 240,00 | 9,0 | 1,80 | 255 |
yg | 240,00 | 9,0 | 1,80 | 255 | |
35 | bk/bl | 336,00 | 10,1 | 2,20 | 348 |
yg | 336,00 | 10,1 | 2,20 | 348 | |
50 | bk/bl | 480,00 | 12,0 | 2,90 | 501 |
yg | 480,00 | 12,0 | 2,90 | 501 | |
70 | bk | 672,00 | 13,6 | 3,70 | 685 |
yg | 672,00 | 13,6 | 3,70 | 685 | |
95 | bk | 912,00 | 15,6 | 4,30 | 902 |
yg | 912,00 | 15,6 | 4,30 | 902 |