JE-H(ST)H BMK ...Bd E30 | Halogen-Free and Flame Retardant Installation Cable for Fire Detection Circuits with Circuit Integrity of 30 Minutes
Item descriptions
Application: | Suitable for fixed installations in fire detection circuits. They are to be used in locations with fire hazard and where an insulation integrity of at least 180 minutes and a circuit integrity of at least 30 minutes are required. |
Construction: | 1.....solid bare copper 2.....core insulation of halogen-free, similar ceramic polymer compound (HI 1), twisted 3.....layer of plastic foil 4.....static screen of plastic coated aluminium foil with a solid tinned drain wire 0,8 mm 5.....outer sheath of halogen-free polymer (HM 2) red with the marking 'BRANDMELDEKABEL' (fire alarm cable) |
Information: | These cables fulfil the conditions of the tests to insulation integrity according to DIN VDE 0472-814/ 8.83 about 180 min. and IEC Public. 331 first edition 1970 to circuit integrity about 30 min.to DIN 4102-12 according to VDE 0100-710 and 0100-718. |
Standards: | DIN VDE 0815 (core identification) DIN EN 60228 class 1 (construction) DIN VDE 0207-24 |
Technical data:
Peak operating voltage | [V] | 225 Volt | |
Temperature range | in motion | - 5°C till +50°C | |
fixed | -30°C till +70°C | ||
Bending radius | in motion | x diameter | 7,5 |
Flammability | standard | EN 50266-2-4 EN 60332-1 | |
standard | IEC 60332-3 Kat.C | ||
Insulation resistance | min. | [MOhm/km] | 100 |
Mutal capacitance | [Ohm/km] | 73,2 | |
max. | [nF/km] | 120 | |
Capacitance unbalance 100m | max | [pF] | 200 |
Number of pairs and nominal conductor diameter mm | Copper figure kg/km | Insulation thickness mm | Overall diameter appr.mm | Calorific potential kWh / m | Weight appr. kg / km |
2 x 2 x 0,8 | 24,00 | 1,0 | 6,6 | 0,13 | 61 |
4 x 2 x 0,8 | 43,20 | 1,0 | 8,8 | 0,20 | 104 |
8 x 2 x 0,8 | 81,60 | 1,2 | 12,8 | 0,34 | 218 |
12 x 2 x 0,8 | 120,96 | 1,2 | 13,5 | 0,39 | 235 |
20 x 2 x 0,8 | 197,76 | 1,4 | 16,1 | 0,53 | 367 |