JB-Y(ST)Y | Fire Alarm Cable
Item descriptions
Application: | They are suitable for fixed installation indoors and are used for fire alarm systems. |
Construction: | 1.....solid bare copper, Ø 0,8mm 2.....core insulation of polyvinylchloride (PVC) 3.....static screen of plastic coated aluminium foil with a drain wire 4.....outer sheath of polyvinylchloride (PVC), red with the marking 'BRANDMELDEKABEL' (fire alarm cable) |
Standards: | DIN VDE 0815 (core identification) DIN EN 60228 class 1 (construction) |
Peak operating voltage | [V] | 300 Volt | |
Test voltage at 50 Hz | core / core | [V]AC | 800 |
core / screen | [V]AC | 800 | |
Temperature range | in motion | - 5°C till +50°C | |
fixed | -30°C till +70°C | ||
Bending radius | in motion | x diameter | 15 |
Flammability | standard | EN 60332-1-2 | |
Insulation resistance | min. | [MOhm/km] | 100 |
Mutal capacitance | [Ohm/km] | 73,2 | |
max. | [nF/km] | 100 |
Number of cores and nominal conductor diameter mm | Copper figure kg/km | Insulation thickness mm | Overall diameter appr.mm | Weight appr. kg / km |
1 x 2 x 0,8 | 10,56 | 1,1 | 5,5 | 38 |
2 x 2 x 0,8 | 20,16 | 1,1 | 6,1 | 54 |
4 x 2 x 0,8 | 39,36 | 1,1 | 8,7 | 94 |
5 x 2 x 0,8 | 49,92 | 1,1 | 9,4 | 114 |
6 x 2 x 0,8 | 59,52 | 1,1 | 10,1 | 135 |
10 x 2 x 0,8 | 98,88 | 1,3 | 13,1 | 205 |
12 x 2 x 0,8 | 118,08 | 1,3 | 13,5 | 235 |
20 x 2 x 0,8 | 194,88 | 1,3 | 15,6 | 352 |
30 x 2 x 0,8 | 291,84 | 1,5 | 19,4 | 522 |
40 x 2 x 0,8 | 387,84 | 1,5 | 20,9 | 663 |
50 x 2 x 0,8 | 484,80 | 1,7 | 23,7 | 832 |