J-Y(ST)Y EIB / KNX | MSR Installation Cable with Static Screen European Installation Bus
Item descriptions
Application: | The installation in, on and under the wall surface, in dry, humid and wet locations as well as outdoors (if protected) is admissible. As BUS-installation cable (EIB-installation bus) it may be used in HV and LV installations, as control and instrumentation cable (MSR-cable) in HV installations. Suitable for the transmission of measuring data, for the installation in the processing and for the application in the field of the control technology. |
Construction: | 1.....solid bare copper 2.....core insulation of polyvinylchloride (PVC) 3.....layer of plastic foil 4.....static screen of plastic coated aluminium foil with drain wire 5.....outer sheath of polyvinylchloride (PVC) green or grey |
Information: | Cores twisted to starquads. (see technical attachment) |
Standards: | DIN VDE 0815 (core identification) DIN EN 60228 class 1 (construction), EIBA spezification |
Peak operating voltage | [V] | 300 | |
Temperature range | in motion | -5°C till +50°C | |
max. on conductor | +70°C | ||
Conductor resistance | max. | [Ohm/km] | 73,2 |
Insulation resistance | min. | [MOhm/km] | 100 |
Mutal capacitance | at 800 Hz | [nF] max. | 100 |
Test voltage | Core / Core | [KV] 5min. | 1 |
Core and Screen on conductorsurface | [KV] 1min. | 4 | |
Bending radius | x diameter | 15 |
Number of pairs and nominal conductor diameter mm | Copper figure kg/km | Overall diameter appr.mm | Weight appr. kg / km |
2 x 2 x 0,8 | 20,16 | 6,6 | 60 |